NOT Authenticated
 
PM Series parameters:
Input rated voltage
Input voltage range
Input voltage derating
Rated frequency range
Input rated current (rated load)
Starting current limiter
Switch-on time
Power factor
Input fuse internal
Recommended back-up fuse (circuit breaker)
Mains buffering (rated load)
Transient surge voltage protection
Output rated voltage
Output voltage range
Output rated current
Output limited current
Class 2 output (UL Limited Power Source, LPS)
Parallel connection
Serial operation
Power dissipation, no load/rated load
Max. power losses
Ripple factor
Resistance to reverse feed max.
Over-voltage-protection
Efficiency
Status indicator
Signal output
Approvals
Storage temperature
Ambient temperature
Derating
Mounting position
Type of cooling
Required minimum spacing (left/right)
Required minimum spacing (over/under)
Protection index
Safety class
MTBF in acc. IEC 61709 (SN 29500)
Terminals input (direct plug-in technology Push-in)
Terminals output (direct plug-in technology Push-in)
Terminals signalling (direct plug-in technology Push-in)
Dimension (W x H x D)
Weight
 
PM-0112-020-0
 
100 - 240 Vac
85 - 264 Vac (120 - 373 Vdc)
-2.5 %/Vac < 95 Vac
44 Hz - 66 Hz / 0 Hz
0.44 A (100 Vac) / 0.22 A (240 Vac)
< 30 A, NTC
1.5 s (100 Vac) / 0.4 s (230 Vac)
0.48
2:00 AM
6 A, 10 A, 16 A, characteristic B, C
15 ms (100 Vac) / 120 ms (230 Vac)
Varistor
12 Vdc
11.5 – 14.5 Vdc
2:00 AM
2.2 ... 2.4 A (constant current)
Yes
Yes
Yes
0.7 W / 5,3 W (230 Vac)
5.7 W (100 Vac / 12 V / 2 A)
typ. 20 mVss
25 Vdc
max. 35 Vdc
82 %
LED green Uout > typ. 10 Vdc LED lit permanently
Active high signal Uout > typ. 10 Vdc max. 40 mA@12 Vdc short circuit proof
cURus, cULus, GL
-25 °C to +85 °C
-25° C to +70° C
-3 %/K > +50 °C
horizontal for standard rail DIN TS35
Natural convection
0 mm
50 mm
IP 20
II, without PE connection
> 500 000 h
max 2,5 mm?
max 2,5 mm?
max 2,5 mm?
22.5 x 90 x 90.5 mm
0.13 kg

© UAB "SANTAVILTĖ"