BUS Terminals communication parameters
Technology
Data transfer channels
Load
Data transfer rates
Line impedance
Bit distortion
Cable length
“0“ signal voltage
“1“ signal voltage
Power supply
Current consumption K-bus
Current consumption power contacts
Electrical isolation
Data buffer
Bit width in the process image
Configuration
Special features
Weight
Operating/storage temperature
Relative humidity
Vibration/shock resistance
EMC immunity/emission
Protect. class/installation pos.
Pluggable wiring
Approvals
 
KL6201
 
AS-Interface
1
-
-
-
-
-
-
-
-
typ. 55 mA (K-bus), approx. 60 mA (AS-Interface)
– (no power contacts)
500 V (AS-Interface/K-bus)
-
selectable: 12 bytes, 22 bytes or 38 bytes, of which 6 bytes parameter interface
via fieldbus parameter interface, DP-V1 or Bus Coupler through KS2000
Slave types: digital and analog, Number of slaves: 31 for V 2.0, 62 for V 2.1
approx. 55 g
0…+55 °C/-25…+85 °C
95 %, no condensation
conforms to EN 60068-2-6/EN 60068-2-27
conforms to EN 61000-6-2/EN 61000-6-4
IP 20/variable
for all KSxxxx Bus Terminals
CE, UL, Ex